This fire alarm and security system is exclusively designed to meet the safety requirements and to protect the unmanned equipment rooms, microwave stations, exchanges etc. from unpredictable events such as fire, unauthorized intrusion, robbery etc.
E 71 comprises four independent sections which continuously monitor the protected premises and on generation of any alarm i.e. fire, door, motion & mains fail alarm. This system offers four independent potential free contacts for extension of remote alarm to operator.
System basic features
[a] Fire alarm
[b] Intruder alarm
[c] Motion Detection alarm
[d] Mains Fail alarm
[a] Fire alarm: The control panel generates audiovisual alarm on receipt of trigger commands from fire sensor. Special tones are used to indicate the fire condition. This will alert the local staff so as to activate the firefighting device or to take other appropriate measures.
[b] Intruder alarm: Unmanned equipment rooms such as microwave stations or exchanges are monitored and protected from unauthorized entry. For this purpose magnetic door sensors are used to trigger the control circuit that generates the audiovisual alarm.
[c] Motion detection alarm: System provides audiovisual alarm whenever motion is detected within the shelter.
[d] Mains fail alarm: System provides alarm for mains fail. Normally Closed (NC) type contact.
All above sections continuously monitor the protected premises and generates respective alarms and also provide the trigger signal for remote alarms through potential free relay contacts. Those individual alarms can be further sent to the central control station or switch room.
System configuration
a] Fire zone : One
b] Fire sensor : Apollo optical smoke sensor.
c] Door sensor : Magnetic door sensor
d] Motion sensor : Passive Infrared Sensor
e] Front panel controls : Self-Test switch for system functionality check
Digital reset switch for fire alarm
Rocker switch for hooter mute
Audiovisual indications
01] System on : Green indicator
02] Mains fail : Amber indicator
03] Low bat : Red indicator
04] Fire : Flashing twin red LED & fire tone by internal & external hooter
05] Fire sensor open : Amber indicator& fault tone by internal Speaker
06] Fire sensor short : Amber indicator & fault tone by internal speaker
07] Door open : Red indicator & beeper tone
08] Motion Detected : Red indicator & external hooter
Remote alarms
All remote alarms are separately provided through potential free relay contacts. All relays remain normally open / normally close as per your requirement and offers short contact during alarm condition.
Electrical specifications
a] Operating supply : 230 VAC +/- 10%, single phase @ 50 Hz.
b] Battery backup : Through 6 V/4.5Ah (2 Nos.) Battery backup Approx. 10 Hrs.
b] Power consumption : Min 1.5 W to Max 15.0 W
Mechanical specifications
a] Panel size : H X W X D 260 X 210 X 90 MM
b] Panel weight : 2.3 Kg (excluding sensors)
c] Panel color : Off white with polycarbonate front sticker
d] Panel mounting : Vertical wall mounting