This fire, intruder & temperature alarm system is specially designed to meet the safety requirements and to protect the unmanned equipment rooms, microwave stations, exchanges etc. from unpredictable events such as fire, unauthorized intrusion and unsafe room temperature.
E 31D comprises three independent sections which continuously monitor the protected premises and on generation of any alarm i.e. fire, door & temperature alarm, this system offers audiovisual local alarms as well as potential free relay contacts for remote alarm.
System basic features
[a] Fire alarm
[b] Intruder alarm
[c] Temperature high alarm
[a] Fire alarm: The control panel generates audiovisual alarm on receipt of trigger commands from fire sensor. Beeper tones are used to indicate the fire condition. This will alert the local staff so as to activate the firefighting device or to take other appropriate measures.
[b] Intruder alarm: Unmanned equipment rooms such as microwave stations or exchanges are monitored and protected from unauthorized entry. For this purpose magnetic door sensors are used to trigger the control circuit that generates the audiovisual alarm.
[c] Temperature alarm: The room temperature is continuously monitored by control panel. For this purpose RTD sensor is used, that senses the room temperature and if it is exceeds the safe limit, system triggers the visual and remote alarms.
All above sections continuously monitor the protected premises and generates respective alarms and also provide the trigger signal for remote alarms through potential free relay contacts. Those individual alarms can be further sent to the central control station or switch room.
Optional feature: Fire II Alarm
The control panel generates Second Fire alarm, which can be used to trip the mains supply, AC, or for other requirement of user.
System configuration
a] Fire zone : One
b] Fire sensor : Apollo optical smoke sensor ( 1 to 4 nos.)
c] Door sensor : Magnetic door sensor
d] Temperature sensor : Temperature sensor (RTD)
e] Front panel controls : Tact switch for
1) System check
2) Fire alarm / sounder mute
3) Arm/Disarm for intruder alarm
4) Temperature selection & set switch
Audiovisual indications
01] System on : Green indicator
02] Fire : Flashing twin red indicator & beeper tone
03] Fire sensor open : Amber indicator & beeper tone
04] Fire sensor short : Amber indicator & beeper tone
05] Door armed : Green indicator
06] Door open : Red indicator & beeper tone
07] Exit delay on : Red indicator & beeper tone
08] Temperature high : Red indicator
09] Temperature Display : Red LED display
Remote alarms
All remote alarms are separately provided through potential free relay contacts. However NC / POLE / NO terminal is provided on main card for selection of alarm type as per user requirement.
Electrical specifications
a] Operating supply : 48 VDC +/- 15%
b] Power consumption : Min 1.5 W to Max 15.0 W
Mechanical specifications
a] Panel size : H X W X D 240 X 185 X 70 MM
b] Panel weight : 1.5 Kg. (excluding sensors)
c] Panel color : Off white with polycarbonate front sticker